| MODEL |
SSP3115C 1-12KVA |
| 1KW |
1.5KW |
2KW |
3KW |
4KW |
5KW |
6KW |
8KW |
10KV |
12KW |
| Input wave form |
Sine wave (utility or generator) |
| Normal voltage |
120VAC(option) 230VAC |
| Low voltage re trip |
90V±4% & 184V/154V±4% |
| Low voltage re engage |
100V±4% & 194V/164V±4% |
| High voltage re trip |
140V±4% & 253V±4% |
| High voltage re engage |
135V±4% & 243V±4% |
| Normal input frequency |
50Hz/ 60Hz (auto detection) |
| Frequency range |
47Hz ~65Hz |
| Output Wave form |
(Bypass mode)same as input |
| Over-Load Protection |
Circuit breaker |
| Short circuit Protection |
Circuit breaker |
| Efficiency on line transfer mode |
>95% |
| Line transfer time |
10ms Typical |
| Bypass without battery connected |
Yes |
| Inverter output |
| Output wave form |
Pure sine wave |
| Output continuos power watts |
1000 |
1500 |
2000 |
3000 |
4000 |
5000 |
6000 |
8000 |
|
12000 |
| Output continuos power VA |
1000 |
1500 |
2000 |
3000 |
4000 |
5000 |
6000 |
8000 |
|
10000 |
| Power factor |
0.9-1.0 |
| Nominal Output Voltage rms |
120VAC(option) 230VAC |
| Output Voltage regulation |
+/- 10%rms |
| Output frequency |
50Hz ± 0.3Hz or 60Hz ± 0.3Hz |
| Short circuit Protection |
Yes ,fault after 1 secs |
| Inverter specification/input |
| Nominal input voltage |
12V/24V/48V |
96V
|
| Minimum start voltage |
10V/20V/40V |
80V |
| Low battery alarm |
10.5V/21V/42V |
84V |
| Low battery trip |
10V/20V/40V |
80V |
| High voltage alarm |
16V/32V/64V |
128V |
| Charger |
| Output voltage |
Dependent on battery type |
| Charge current |
10-85A MAX |
35A MAX |
45A MAX |
|
50A MAX |
| Battery initial voltage for start up |
0-15.7v for 12v(*2 for 24v;*4 for 48v) |
| Over charge protection |
15.7v for 12v(*2 for 24v;*4 for 48v) |
| Solar Charge |
| MPPT Range@Operating Voltage |
15VDC~150VDC / 25VDC~150VDC / 60VDC~150VDC |
100VDC~300VDC |
| Maximum PV Array Open Circuit Voltage |
150VDC |
300VDC |
| Maximum Charging Current |
40A/60A |
| Maximum Effciency |
>96% |
| Standby Power Consumption |
2W |